JOINTS · FOR ALUMINUM CONDUCTORS · MEDIUM VOLTAGE

Previous

TERMINAL LUGS FOR ALUMINUM CONDUCTORS · UNINSULATED · DIN 48201

Previous

REDUCTION JOINTS · FOR ALUMINUM OR COPPER CONDUCTORS · MEDIUM VOLTAGE

Product Categoryjoint
Terminal materialaluminum with no less than 99.5% purity
Operating temperaturefrom -50 °C to +150 °C
Voltageup to 35 kV
Protectionthe conductor housing is filled with grease (dropping point 90°C) and plugged with a plastic cap to avoid oxidation.
Typewith central diaphragm for a right insertion of the conductor.
The diaphragm is sealed to avoid the mixture of paper filled cables to get in touch with cables with solid insulation.
According to std.DIN 48201
Etim 9EC001060
cid11TG03B
Images with
dimensions
Item
Code
Section
[mm²]
Section
[AWG/MCM]
Indent
[mm]
L1
[mm]
L2
[mm]
D1
[mm]
D2
[mm]
Quantity per
Wishlist
70202 35 ÷ 35(2 - 2)201386720810/10
70203 50 ÷ 50(1/0 - 1/0)201386720910/10
70204 70 ÷ 70(2/0 - 2/0)2013867201110/10
70205 95 ÷ 95(3/0 - 3/0)20138672012,510/10
70206 120 ÷ 120(4/0 - 4/0)25164802513,710/10
70207 150 ÷ 150(300 - 300)25164802515,510/10
70208 185 ÷ 185(400 - 400)3217686321710/10
70209 240 ÷ 240(500 - 500)32176863219,510/10